MENU CONFIGURATION DISPLAYS Table 6-1
Not all menu items display on standard meters.
(Defaults in Bold and Italics)

MENU
/TARE
/MAX
INPT
Show input choices:
100m
▒50m
10 V
▒5 V
0-20
DEC.P
Show current decimal point position
FFFF.
FFF.F
FF.FF
F.FFF
RD.S.O
(Reading Scale & Offset)

Enter new value and show "RD 1"

Enter new value and show "IN 2"
Show IN 1 and prior value entered.

Scroll to the next digit to the right

Show prior value entered.

Scroll to the next digit to the right.

Show RD 2 and prior value entered.

Scroll to the next digit to the right.
Change the value of the flashing digit.




Change the value of the flashing digit.



Change the value of the flashing digit.
MENU
/TARE
/MAX
RD.CF
(Reading Configuration)
R.1=


R.2=

















R.3=
T (Tare enabled)
N (Tare Disabled)

0 (1╡V resolution for unipolar & 5╡V resolution for bipolar)

1 (2╡V resolution for unipolar & 10╡V resolution for bipolar)

2 (3╡V resolution for unipolar & 15╡V resolution for bipolar)

3 (5╡V resolution for unipolar & 25╡V resolution for bipolar)

4 (10╡V resolution for unipolar & 25╡V resolution for bipolar)

Note: 3 ╡V resolution means if your input is 0-30mV, at 30mV the display shows 9999.

F (Filtered value)
U (Unfiltered value)
S1.CF
Setpoint 1 Configuration
S.1=


S.2=

A (Active above)
B (Active below)

U (Unlatched)
L (Latched)
S2.CF
Setpoint 2 Configuration
S.1=


S.2=

A (Active above)
B (Active below)

U (Unlatched)
L (Latched)
S1.DB
Setpoint 1 Deadband
Press to scroll to the next digit to the right Press to change the value of the flashing digit
S2.DB
Setpoint 2 Deadband
Press to scroll to the next digit to the right Press to change the value of the flashing digit
OT.CF*
Output Configuration
0.1=


0.2=


0.3=


0.4=



0.5=
E (Analog output is enabled)
D (Analog output is disabled)

C (Analog output is current)
V (Analog output is voltage)

A (Regular analog output)
P (Proportional analog output)

D (Proportional analog is direct acting)
R (Proportional analog is reverse acting)

F (Analog output is 0-10 Vdc)
H (Analog output is 0-5 Vdc)
Notes: *If yolu select 0.2=V, you may select your analog output to be 0-10 V or 0-5V by accessing sub-menu 0.5=F or 0.5=H

* If 0.3=P, you may select your proportional output analog to be direct 0.4=D (4-20 mA), (0-5V), (0-10v) or reverse acting 0.4=R (20-4 mA), (5V-0V), (10V-0V).
P.BND
Proportional Band shown menu if 0.3=P
Show prior value entered

Scroll to the next digit to the right
Change the value of the flashing digit
M.RST
Manual Reset shown menu if 0.3=P
Show prior value entered

Scroll to the next digit to the right
Change the value of the flashing digit
OT.S.O
(Output Scale & Offset)

Enter new value and show OUT1



Enter new value and show RD 2



Enter new value and show OUT2
Show RD1 and prior value entered

Scroll to the next digit to the right

Show prior value entered.

Scroll to the next digit to the right

Show prior value entered.

Scroll to the next digit to the right
Change the value of the flashing digit




Change the value of the flashing digit



Change the value of the flashing digit
LK.CF
Lock Out Configuration
RS=


SP=


L3=

(Enable RESET button in the run mode
D (Disable RESET button in the run mode)

E (Enable setpoint changes)
D (Disable setpoint changes)

0 (SETPTS button display setpoint values)

1 (SETPTS button display software ôv.-03ö version)

Run Mode Displays
Table 6-2

MENU
/TARE
/MAX
RESET
DESCRIPTION
PEAK
  Displays the peak reading and must be pressed again to return to the normal operating mode without resetting. Reset the peak reading when in this mode. Peak Reading
Displays the highest reading since last reset.
T.RST
Press to activate   Will reset your tare when viewing this function Tare Reset
SP.RS
      Reset Latched Alarms
Pressing the RESET button resets your latched alarms.